Case Study Viewer

Vihaistenkari Day Care Center, Raahe, Finland
Heating
The consumptions of SF2, MWh
year MWh MWh (normalized)
1998 175,2 163,4
1999 168,3 165,8
2000 170,9 187,4
2001 190,2 186,5
2002 203,2 198,7

The heating energy consumption has not reduced.
There are obvious reasons why the amount of heating energy has increased. When the ventilation system has been renovated, no other repairs were done. In new conditions, part of the supply air is coming through the leakage in untight areas of external walls. The heat recovery unit actually processes only one part of the incoming air.

Electrical Energy